Installer Setup (ISU)
New Installation
-
After the thermostat has powered up, touch GET STARTED on the thermostat.
-
After selecting the correct option for each setting, Touch NEXT at the bottom of the display to advance to the next option.
-
To see a list of all setup parameters, go to Installer Setup Options (ISU). The thermostat displays the ISU name.
-
To finish setup and save your settings, touch Done in the upper left of display.
Revising Settings
If this is not a new installation and you want to access the Installer setup to change settings:
-
Touch the Menu icon (3 horizontal lines at bottom of display).
-
Scroll down and touch Thermostat Information.
-
Write down the date code from that screen. The touch the left arrow at top of display to go to previous screen.
-
Scroll down until Installer Options is shown. Touch Installer Options and enter date code.
-
Select Installer Setup.
-
After selecting the correct option for each setting, Touch NEXT at the bottom of the display to advance to the next option.
-
To see a list of all setup parameters, go to Installer Setup Options (ISU).
-
To finish setup and save your settings, touch Done in the upper left of display.
Installer Setup Options (ISU)
NOTE: Firmware is occasionally updated at the factory or over the air. Some ISU settings may not be shown on models that lack the latest firmware. Light commercial and fan coil unit settings available on T10+ with firmware 03.03.08.02 or later)
|
ISU # |
Heading |
Question |
Options |
Contingent previous setting? |
EIM needed? |
T10, T10+ or both |
Notes |
|---|---|---|---|---|---|---|---|
|
1000 |
Language |
What language would you like to use? |
|
|
No |
Both |
ISU number not displayed during initial setup |
|
1010 |
Application |
What type of installation will this thermostat be used for? |
|
|
No |
T10+ |
Available on T10+ & EIM with firmware 03.03.08.02 or later |
|
None shown |
Room |
In what type of room will this thermostat be installed? |
|
Options shown vary for Residential or light commercial |
No |
Both (light com-mercial for T10+ only) |
Only shown during initial setup |
|
1030 |
Home Screen |
Would you like the device name displayed on the home screen? |
|
1010 = light commercial |
No |
T10+ |
|
|
1050 |
Temperature Format |
Which temperature scale would you like to use? |
|
|
No |
Both |
|
|
No ISU number |
Equipment Interface Module |
Do you have an Equipment Interface Module (EIM)? |
|
|
|
T10+ |
Only shown during initial setup |
|
No ISU number |
Wireless setup |
Press and release CONNECT button on the Equipment Interface module (EIM). When the Connect light is flashing green on the EIM, then press Next. |
NEXT |
|
Yes |
T10+ |
Only shown during initial setup |
|
1055 |
Floor sensor |
Floor sensor |
|
|
No |
T10+ |
|
|
1060 |
Outdoor Temperature |
Outdoor Temperature |
(*Wireless automatically selected if sensor added during setup) |
Wireless only shown if C7089R3013 has been linked to T10+ during setup. |
No |
See notes |
*T10 & T10+ have this setting but wireless outdoor sensor only for T10+ |
|
2000 |
System Type |
System Type |
|
|
No |
Both |
*Fan coil option only shown here for T10+ with firmware 03.03.08.02 or later. For older firmware and T10 models: If you select Conventional Forced Air here, you will get the option for Hot Water Fan Coil in 2010. |
|
2010 |
Equipment type |
Equipment type |
|
2000 = Conventional Forced Air Heat |
No |
Both |
*If a T10+ with firmware 03.03.08.02 or later, there is a setting for Fan Coil under 2000 (row above). When selected, you will see options for Hot Water Fan Coil, 2-pipe, or 4-pipe in ISU 2010 |
|
Equipment type |
|
2000 set to Heat Pump |
No |
Both |
|
||
|
Equipment type |
|
2000 = other |
No |
Both |
|
||
|
Equipment type |
|
2000 set to Radiant Heat |
No |
Both* |
*Hot water radiant floor heat for T10+ only |
||
|
Equipment type |
|
2000 = fan coil |
No |
2-pipe and 4-pipe for T10+ only. Added with Firmware 03.03.08.02 or later |
|||
|
2054 |
Fan coil |
Changeover sensor |
|
2010 = 2-pipe |
No |
T10+ |
Method for T10+ to determine if pipe is hot or cold.
The 2-pipe FCU wiring diagrams show how this should be wired to the T10+ or EIM |
|
2055 |
Fan coil |
Changeover sensor setup |
|
2054 = dry contact |
No |
T10+ |
|
|
2056 |
Fan coil |
Changeover wiring assignment |
|
2054 = 10K or 20K |
No |
T10+ |
|
|
2060 |
Reversing Valve |
Reversing Valve |
|
2000 set to Heat Pump |
No |
Both |
|
|
2070 |
Equipment stages |
Cool stages |
|
2000 set to other than Heat Pump |
EIM needed for 4 cool stages |
Both |
|
|
Heat stages |
|
|
No |
Both |
|
||
|
Radiant Heat Stages |
|
1055 set to Wired or 2000 = Radiant Heat |
No |
Both |
|
||
|
Compressor Stages |
|
2000 set to Heat Pump |
No |
Both |
|
||
|
Fan Coil Heat Stages |
|
2010 = Hot Water Fan Coil |
See notes |
Both |
EIM needed for 3 stages |
||
|
Electric Forced Air Heat Stages |
|
2010 = Electric Forced Air |
See notes |
Both |
EIM needed for 3 stages. |
||
|
Fan coil stages |
|
2000 = fan coil |
No |
T10+ |
|
||
|
Backup Heat Stages |
|
2000 set to Heat Pump or 2-Pipe Fan Coil |
See notes |
Both |
*2 only shown for heat pump and using EIM |
||
|
2080 |
Terminal assignment |
What terminals are wired to cool stage 3? |
|
2070 = 3 or 4 Cool stages |
No |
T10+ |
See wiring diagrams for cool 3-4 wiring. |
|
2090 |
Terminal assignment |
What terminals are wired to cool stage 4?
|
|
2070 = 4 Cool stages |
Yes |
T10+ |
|
|
2105 |
Fan Control |
Fan stages |
|
2010 = 2-pipe or 4-pipe Fan Coil |
No |
T10+ |
During setup, T10+ instructs where to wire this to. There are also wiring diagrams in this file. * If only 2 fan speeds are used, ISU 2106 will say High Speed rather than Medium Speed |
|
2106 |
Fan Coil |
Medium * Fan Speed Wiring Assignment |
|
2105 = 2 - 3 |
No |
T10+ |
|
|
2107 |
Fan Coil |
High * Fan Speed Wiring Assignment |
|
2105 = 3 |
No |
T10+ |
|
|
2110 |
Fan Control |
Fan Operation in Heat |
|
2010 = other, Electric Forced Air |
No |
Both |
|
|
2120 |
Backup heat type |
Backup heat type |
|
1055 = wired floor sensor, or 2000 = Radiant Heat |
No |
Both |
|
|
2130 |
Backup heat stages |
Backup heat stages |
(Only 1 if 2070 = 2 Radiant Heat stages) |
ISU 1055 = Wired or 2000 = Radiant & 2120 = other than None |
No |
Both |
* EIM needed for 2 backup stages. |
|
2150 |
Backup Heat operation |
Backup Heat operation |
|
2010 = Hot Water Fan Coil and 2130 = other than 0 |
No |
T10+ |
|
|
2160 |
Fan Control |
Backup Heat Fan Control |
|
Typically shown if backup heat = electric, hot water coil, or other |
No |
Both |
|
|
2175 |
Backup Heat |
Aux/E Terminal Control |
|
2070 Backup Heat stages = 1 |
No* |
Both |
*2175 is not shown and defaults to drive aux and E together when EIM is used. |
|
2180 |
Backup Heat |
Backup Heat Type |
|
2070 Backup Heat stages = 1 or 2 |
No |
Both |
|
|
2185 |
Emergency Heat |
Emergency Heat Type |
|
2175 = independent |
No* |
Both |
*2175 & 2185 are not an option when EIM is used. |
|
2190 |
External Fossil Fuel Kit |
External Fossil Fuel Kit |
|
2000 = heat pump, 2180 = Gas or oil forced air |
No |
Both |
When set for external fossil fuel kit, the thermostat may run the heat pump and backup heat at the same time, assuming the external fossil fuel kit will do the lockouts |
|
2200 |
Backup Heat Operation |
Backup Heat Operation |
|
2180 set for Hot Water or Other |
No |
Both |
|
|
2205 |
Emergency Heat Operation |
Emergency Heat Operation |
|
2150 set for Hot Water or Other |
No* |
Both |
*2175 and 2205 are not options when EIM is used. |
|
2210 |
Fan Control
|
Backup Heat Fan Operation |
|
2180 = Hot water fan coil or other |
No |
Both |
|
|
2215 |
Emergency Heat Fan Operation |
2185 = Hot water fan coil or other |
No |
Both |
|
||
|
2216 |
Economizer/ Time of Day |
Economizer / Time of Day |
|
1010 = Commercial |
No |
T10+ |
See wiring diagrams for Economizer |
|
2217 |
Economizer |
What terminals are wired to the Economizer output? |
|
2216 = Economizer |
No |
T10+ |
See wiring diagrams for Economizer |
|
2218 |
Time of Day |
What terminals are wired to the Time of Day output? |
|
2216 = Time of Day |
No |
T10+ |
See wiring diagrams for Time of Day |
|
2220 |
L Terminal alert |
What is the L Terminal used for? |
|
Options shown if ISU 2000 = heat pump or 2216= Economizer. If 2054 = Dry Contact, then 2220 is not shown |
No |
T10+ |
|
|
2230 |
Control mode |
Control Mode |
|
1055 set to Wired |
No |
T10+ |
No Floor only option if there is a Cool stage or Backup Heat stage. |
|
2240 |
Occupancy sensing |
Remote Setback |
|
Wireless sensor(s) option requires C7189R2002 or C7189R3002 wireless indoor sensor(s) |
No |
T10+ |
See the Remote Setback (Occupancy Sensing) sections for the uses of this setting, its operation and its wiring options |
|
3000 |
Changeover |
Changeover |
|
Any system with at least 1 Heat stage & 1 Cool stage |
No |
Both |
|
|
3015 |
Auto Changeover Differential |
0-5F (0.00 to 2.50C) |
3000= auto |
No |
Both |
|
|
|
3020 |
Staging control |
Finish with high cool stage |
|
2 cool/ compressor stages |
No |
Both |
|
|
3021 |
Staging control |
Finish with high heat stage |
|
At least 2 heat stages |
No |
Both |
|
|
3030 |
Staging control |
Cool differential stage 2 |
|
2 cool stages selected |
No |
Both |
|
|
3050 |
Staging control |
Radiant heat differential |
|
There are 2 stages of radiant heat selected for 2070. |
No |
Both |
|
|
Heat Differentials |
Stage 2:
|
2000 = Conventional Forced air + 2070 = 2 or 3 |
No |
T10+ |
|
||
|
Stage 3:
|
2000 = Conventional Forced air + 2070 = 3 |
Yes |
T10+ |
|
|||
|
3060 |
Staging control |
Compressor Heat Differential Stage 2 |
|
2000 = Heat Pump and 2070 Compressor stages = 2 |
No |
Both |
|
|
3080 |
Staging control |
Backup Heat differentials |
Stage 1:
|
Radiant heat with 1 or 2 backup heat stages |
No |
Both |
*If 2 stages of backup heat. The 2nd backup stage is forced to be at least .5 degrees higher than first stage Backup Heat. |
|
Stage 2:
|
Radiant heat with 2 backup heat stages |
Yes |
T10+ |
||||
|
3090 |
Staging control |
Backup Heat differentials |
Stage 1:
|
Heat pump of FCU with 1 or 2 backup heat stages |
No |
Both |
*Comfort setting not available for Dual Fuel.
See section on Backup heat differentials, Upstage Timer, and Holdoff Timer.
For an FCU, the thermostat will automatically switch to Em Heat mode and run the backup heat if the thermostat had been in heat mode and pipe sensor detects pipe is no longer in the heat temperature threshold.
If you don’t want to switch to the backup heat when that pipe is warm, set a high Differential setting and set the timers to the maximum settings. |
|
Stage 2:
|
Heat pump selected with 2 Backup Heat stages |
Yes |
T10+ |
||||
|
3110 |
Staging control |
Backup heat upstage timer |
|
3090 set for other than “Comfort” |
No |
Both |
|
|
Backup Heat holdoff timer |
|
Upstage timer set to other than “Off”. |
No |
T10+ |
|||
|
3120 |
Equipment Lockouts |
Compressor Lockout/Balance point |
|
Configured for heat pump with an Aux Heat stage |
No |
Both |
|
|
Backup Heat Lockout |
|
No |
Both |
|
|||
|
3125 |
Equipment Lockouts |
Fan Lockout after cool call ends |
|
2070 = at least 1 cool/compressor stage |
No |
T10+ |
This locks out the fan after a cool call even if the fan is set to On or Circ mode or if the fan is set to run for air temperature balancing. |
|
3130
|
Cycle rates
|
Stage 1 Radiant Heat Cycle rate |
|
At least 1 radiant heat stage |
|
|
|
|
Stage 2 Radiant Heat Cycle rate |
|
Two radiant heat stages |
|
|
|
||
|
3140 |
Cycle rates |
Stage 1 Cool Cycles Per hour |
|
2000 = other than heat pump. 2070 = 1 -4 cool stages |
No |
Both |
|
| Stage 2 Cool Cycles Per hour |
|
2000 = other than heat pump. 2070 = 2-4 cool stages |
No |
Both |
|
||
|
Stage 3 Cool Cycles Per hour |
|
2070 = 3-4 cool stages |
No |
T10+ |
Can use U contacts on thermostat without EIM for stage 3. EIM is needed for stage 4 since it has 3 sets of U.
|
||
|
Stage 4 Cool Cycles Per hour |
|
2070 = 4 cool stages |
Yes |
T10+ |
|||
|
Compressor Cycles Per Hour |
Stage 1:
|
2000 = heat pump |
No |
Both |
|
||
|
Stage 2:
|
2000 = heat pump, 2070 = 2 |
No |
Both |
|
|||
|
3150 |
Cycle rates |
Radiant Heat cycles per hour |
Stage 1
|
At least 1 Radiant Heat stage |
No |
Both |
|
|
Stage 2
|
2 Radiant Heat stages |
No |
T10+ |
|
|||
|
Heat Cycles per hour |
Stage 1
|
2000 = Conventional Forced Air, or Other |
No |
Both |
|
||
|
Stage 2
|
2000 = Conventional Forced Air & 2070 = 2-3 heat stages |
No |
Both |
|
|||
|
Stage 3
|
2000 = Conventional Forced Air & 2070 = 3 heat stages |
Yes |
T10+ |
|
|||
|
|
Primary Heat Cycles per hour |
Settings 1-12 |
2010 = other |
|
T10+ |
Added to firmware versions 03.03.08.02 and later |
|
|
3160 |
Cycle rates |
Backup heat cycles per hour |
Backup heat cycles per hour
|
2130 = at least 1 Backup Heat stage selected |
No |
Both |
|
|
Backup heat cycles per hour |
Backup heat cycles per hour stage 2
|
2130 = 2 Backup Heat stage selected |
Yes |
T10+ |
|
||
|
3240 |
Temperature Control |
Minimum Compressor or Fan Coil Off Time |
Settings:
|
|
|
|
When set for a heat pump or conventional cool stage this setting is minimum Compressor off time. When set for a 2-pipe or 4-pipe fan coil it will be minimum fan coil off time |
|
3250 |
Temperature Control |
Minimum non-compressor on time |
|
2000 = Radiant Heat |
No |
T10+ |
|
|
3260 |
Temperature Control |
Extended fan run times |
Extended fan run time in Cool:
|
At least 1 cool stage |
No |
Both |
|
|
Extended fan run time in Heat:
|
At least 1 Heat stage |
No |
Both |
|
|||
|
3300 |
Temperature Control |
Temperature Balancing |
|
|
No |
T10+ |
|
|
3310 |
Temperature Control |
Temperature Balancing Room Delta |
|
|
|||
|
3320 |
Fan Control |
Fan Modes Allowed |
|
2105 = 2 or 3 |
No |
T10+ |
For settings and options:
|
|
3325 |
Fan Control |
Start Fan on the Highest Stage |
|
2105 = 2 or 3 |
|
T10+ |
|
|
3340 |
Fan Control |
Fan reset to Auto Mode timer |
|
2010 = 2-pipe or 4-pipe |
|
T10+ |
|
|
4010 |
Fan Control |
Pre-Occupancy Purge Duration |
|
1010 = Light Commercial |
No |
T10+ |
Run fan prior to occupied period |
|
4020 |
Type of Override |
Type of Override |
|
1010 = Light Commercial |
No |
T10+ |
See description in Commercial Features.
|
|
4030 |
Override Duration |
Override Duration |
|
1010 = Light Commercial |
No |
T10+ |
|
|
4050 |
Temperature Control |
Minimum Heat Recovery Ramp Rate (cold day) |
|
1010 = light commercial.
1060 (Outdoor Temperature) must be set to other than “None”, to see the outdoor temp settings for 4050-4080.
If set to “Wired”, 5050 must also be set to other than “None” |
No |
T10+ |
When set to OFF, The heating system will begin recovery at the time that is scheduled. When a Minimum Recovery Ramp Rate is set, the thermostat will begin recovery early to ensure that the temperature is reached at the scheduled time. Set a Minimum Recovery Ramp Rate based on the rate that the heating system can recover at for a cold day in your region. Default setting is 5F / hour. Set an Outdoor Temperature that is representative of a cold day in your region to be associated with the Minimum Recovery Ramp Rate.The thermostat will begin recovery at the optimal time based on a calculated ramp rate. During recovery, the setpoint changes at a rate in degrees per hour depending on the outdoor sensor, the Minimum Recovery Ramp Rate is used. |
|
Outdoor Temperature used with Minimum Heat Recovery Ramp Rate |
|
||||||
|
4060 |
Temperature Control |
Maximum Heat Recovery Ramp Rate (mild day) |
|
When set to Off, the heating system will begin recovery at the time that is scheduled. When a Maximum Recovery Ramp Rate is set, the thermostat will begin recovery early to ensure the temperature is reached at the scheduled time. Set a Maximum Recovery Ramp Rate based on the rate that the heating system can recover at for a mild day in your region. Default setting is 8° F / hour. Set an Outdoor Temperature that is representative of a mild day in your region to be associated with the Maximum Recovery Ramp Rate. The thermostat will begin recovery at the optimal time based on a calculated ramp rate, allowing the system to recover on time and save energy during changing outdoor conditions. During recovery, the setpoint changes at a rate in degrees per hour depending on the outdoor temperature. | |||
|
Outdoor Temperature used with Maximum Heat Recovery Ramp Rate |
|
||||||
|
4070 |
Temperature Control |
Minimum Cool Recovery Ramp Rate (hot day) |
|
When set to OFF, the cooling system will begin recovery at the time that is scheduled. When a Minimum Recovery Ramp Rate is set, the thermostat will begin recovery early to ensure the temperature is reached at the scheduled time. Set a Minimum Recovery Ramp Rate based on the rate that the cooling system can recover at for a hot day in your region. Default setting is 3° F / hour. If an outdoor sensor is installed, set an Outdoor Temperature that is representative of a hot day in your region to be associated with the Minimum Recovery Ramp Rate. The thermostat will begin recovery at the optimal time based on a calculated ramp rate, allowing the system to recover on time and save energy during changing outdoor conditions. During recovery, the setpoint changes at a rate in degrees per hour depending on the outdoor temperature. If there is no outdoor sensor, the Minimum Recovery Ramp Rate is used. | |||
|
Outdoor Temperature used with Minimum Cool Recovery Ramp Rate |
|
||||||
|
4080 |
Temperature Control |
Maximum Cool Recovery Ramp Rate (mild day) |
|
When set to off, the cooling system will begin recovery at the time that is scheduled. When a Maximum Recovery Ramp Rate is set, the thermostat will begin recovery early to ensure the temperature is reached at the scheduled time. Set a Maximum Recovery Ramp Rate based on the rate that the cooling system can recover at for a mild day in your region. Default setting is 6° F / hour. Set an Outdoor Temperature that is representative of a mild day in your region to be associated with the Maximum Recovery Ramp Rate. The thermostat will begin recovery at the optimal time based on a calculated ramp rate, allowing the system to recover on time and save energy during changing outdoor conditions. During recovery, the setpoint changes at a rate in degrees per hour depending on the outdoor temperature. | |||
|
Outdoor Temperature used with Maximum Cool Recovery Ramp Rate |
|
||||||
|
4090 |
Temperature Control |
Adaptive Intelligent Recovery |
|
|
No |
Both |
When schedule is used, this setting brings on heat or cool prior to comfort setpoints to ensure heat/cool settings are reached by the desired times. |
|
4100 |
Range Stops |
Temperature range stops |
Minimum cool setpoint; 50F-99F (10C-37C) |
At least 1 stage of cool |
No |
Both |
There is a correlation between these settings. For example, if minimum cool is set to 50F, minimum heat cannot be set above 40F |
|
Maximum cool setpoint; 90F-99F (32C-37C) |
At least 1 stage of cool |
No |
Both |
||||
|
Minimum heat setpoint; 40F-50F (4.5C-10C) |
At least 1 stage of Heat |
No |
Both |
||||
|
Maximum heat setpoint; 40F-90F (4.5 - 32.0C) |
At least 1 stage of Heat |
No |
Both |
||||
|
4110 |
Keypad lockout |
Keypad lockout |
Unlocked, partially locked, fully locked |
|
No |
Both |
|
|
5000 |
Sensors |
What sensors are WIRED to your system? |
|
Floor sensor only shown here if 1055 is set to Wired. Fan Coil Changeover Temperature only shown if 2054 = 10k or 20k |
No |
Return, Discharge, Floor and Fan Coil Change-over are for T10+ only. |
|
|
5020 |
Sensors |
What Terminals are Wired to the Indoor Temperature Sensor? |
|
5000 has Indoor Sensor selected |
No |
Both |
Options depend on whether EIM is used. |
|
5030 |
Sensors |
Indoor Temperature Sensor Type |
|
5000 has Indoor Sensor selected |
No |
Both |
|
|
5040 |
Sensors |
Which Sensors will be used for TEMPERATURE Control? (Multiple sensors are averaged) |
|
5000 set for Wired Indoor Sensor |
No |
Both |
|
|
5050 |
Sensors |
What Terminals are Wired to the Outdoor Air Temperature Sensor? |
|
1060 set to Wired |
No |
Both |
Options depend on whether EIM is used.
|
|
5070 |
Sensors |
What Terminals are Wired to the Return Air Temperature Sensor? |
|
5000 has Return Sensor selected |
|
T10+ |
Options depend on whether EIM is used. |
|
5080 |
Sensors |
Return Temperature Sensor Type |
|
5000 has Return sensor selected |
No |
T10+ |
|
|
5090 |
Sensors |
What Terminals are Wired to the Discharge Air Temperature Sensor? |
|
5000 has Discharge Sensor selected |
No |
T10+ |
Options depend on whether EIM is used. |
|
5100 |
Sensors |
Discharge Temperature Sensor Type |
|
5000 has Discharge Sensor selected |
No |
T10+ |
|
|
5110 |
Sensors |
A-Coil Low Temperature Cutoff |
|
At least 1 cool stage |
No |
T10+ |
|
|
5120 |
Sensors |
What Terminals are Wired to the Floor Temperature Sensor? |
|
1055 set to “Wired” |
Yes |
T10+ |
Options depend on whether EIM is used. |
|
5150 |
Floor Temperature Limits |
Minimum Limit |
Minimum Limit = 40°F-89°F (4.5°C to 31.5°C) |
ISU 2230 = |
No |
T10+ |
Top range affected by Maximum limit setting |
|
Maximum Limit |
Maximum Limit = 50°F-99°F (10.0°C to 37.0°C) |
No |
T10+ |
Bottom range affected by Minimum limit setting |
|||
|
5160 |
Floor Economy Mode |
Floor Economy Mode |
|
5000 has Floor Sensor selected |
No |
T10+ |
If enabled, Low Floor Temperature Limit (ISU 5150) will be disabled during Away and Sleep period. This ISU is only displayed if Temperature Control Mode (ISU 2230) is set to AF mode. |
|
5170 |
Freeze Protection |
Freeze Protection |
(Off only available for non-radiant systems) |
Cannot be below minimum setting in 5150 (if used). |
No |
T10+ |
The thermostat operates the heat whenever the room temperature falls below that limit, even when the system is set to off. Default setting is Off (disabled) for non-radiant systems and 40°F (4.5°C) for radiant systems. Freeze protection temperature cannot be set above ISU 5150 minimum setting. |
|
5200 |
Changeover Setup |
Temperature Thresholds |
|
5000 = Fan coil changeover |
No |
T10+ |
|
|
6000 |
Dry Contacts |
Select the Dry Contacts in the System |
|
|
Yes |
T10+ |
See Dry Contact Alerts (ISU 6000- 6220) for operation details |
|
6005 |
Custom Dry Contact alerts |
Select Custom Dry Contact alerts |
|
|
Yes |
T10+ |
See Dry Contact Alerts (ISU 6000- 6220) for operation details |
|
6010 |
Dry Contacts |
What terminals are wired to the Remote Setback Dry Contact? |
|
6000 = Remote Setback |
Yes |
T10+ |
|
|
6020 |
Dry Contacts |
Remote Setback Dry Contact Setup |
|
2240 = L terminal or 6010 = S1-S4 |
No |
T10+ |
|
|
6030 |
Dry Contacts |
Remote Setback Time Delayed from Occupied to Unoccupied |
0 Minutes to 30 Minutes in 5 minute increments |
2240 = Other than "None" |
No |
T10+ |
|
|
6040 |
Dry Contacts |
Remote Setback – Standby Cool Setpoint |
72°F-90°F (22.0° - 32.0°C) |
||||
|
Remote Setback – Standby Heat Setpoint |
50°F-70°F (10.0° - 21.0°C) |
||||||
|
6050 |
Dry Contacts |
What terminals are wired to the Full Drain Pan Alert dry contact? |
|
6000 has full drain pan selected |
Yes |
T10+ |
See Dry Contact Alerts (ISU 6000- 6220) for operation details |
|
6060 |
Dry Contacts |
Full Drain Pan Alert dry contact setup |
|
6000 has full drain pan selected |
Yes |
T10+ |
|
|
6065 |
Dry Contacts |
Full Drain Pan Alert dry contact actions |
System shutdown
|
6000 has Full Drain Pan selected |
Yes |
T10+ |
|
|
6070 |
Dry Contacts |
What terminals are wired to the Dirty Filter Alert dry contact? |
|
6000 has Dirty Filter Alert selected |
Yes |
T10+ |
|
|
6080 |
Dry Contacts |
Dirty Filter Alert dry contact setup |
|
Yes |
T10+ |
||
|
6090 |
Dry Contacts |
What terminals are wired to the Water Leak Alert dry contacts? |
|
6000 has water leak selected |
Yes |
T10+ |
See Dry Contact Alerts (ISU 6000- 6220) for operation details |
|
6100 |
Dry Contacts |
Water Leak Alert dry contact setup |
|
6000 has water leak selected |
Yes |
T10+ |
|
|
6110 |
Dry Contacts |
What terminals are wired to the System Shutdown Alert dry contact? |
|
6000 has system shut down alert selected |
Yes |
T10+ |
See Dry Contact Alerts (ISU 6000- 6220) for operation details |
|
6120 |
Dry Contacts |
System shut down alert dry contact setup |
|
Yes |
T10+ |
||
|
6130 |
Dry Contacts |
What terminals are wired to the Service Needed Alert dry contact? |
|
6000 has Service Needed Alert selected |
Yes |
T10+ |
See Dry Contact Alerts (ISU 6000- 6220) for operation details |
|
6140 |
Dry Contacts |
Service Needed Alert dry contact setup |
|
Yes |
T10+ |
||
|
6150 |
Dry Contacts |
What terminals are wired to the Fan Failure Alert dry contact? |
|
6000 has Fan Failure Alert selected |
Yes |
T10+ |
See Dry Contact Alerts (ISU 6000- 6220) for operation details |
|
6160 |
Dry Contacts |
Fan Failure Alert dry contact setup |
|
Yes |
T10+ |
||
|
6190 |
Dry Contacts |
What terminals are wired to the custom alert 1 dry contact? |
|
6005 has custom alert 1 selected |
Yes |
T10+ |
See Dry Contact Alerts (ISU 6000- 6220) for operation details |
|
6200 |
Dry Contacts |
Custom alert 1 dry contact setup |
|
Yes |
T10+ |
||
|
6210 |
Dry Contacts |
Custom Alert 1 Name |
Type in the alert name |
Yes |
T10+ |
||
|
6215 |
Dry Contacts |
Show custom alert 1 message |
|
Yes |
T10+ |
||
|
6220 |
Dry Contacts |
Custom Alert 1 Message |
Type in the message displayed when this alert is active |
6215 set to Yes |
Yes |
T10+ |
See Dry Contact Alerts (ISU 6000- 6220) for operation details |
|
6230 |
Dry Contacts |
Custom alert 1 actions |
|
6005 has custom alert 1 selected |
|
|
|
|
6240 |
Dry Contacts |
What terminals are wired to custom U contact? |
|
6230 has custom U terminal selected |
Yes |
T10+ |
When the switch wired to the S terminals for the Custom Dry Contact Alert activates, the custom U contacts will change state to activate or shut off whatever is wired to those terminals |
|
6250 |
Dry Contacts |
Custom U dry contact name |
Type in the name of whatever the custom U Dry Contact is controlling |
||||
|
6260 |
Dry Contacts |
Custom U dry contact setup |
|
||||
|
6300 - 6370 |
These are duplicate settings to 6190-6260 but for Dry Contact Alert 2 (if selected) |
6005 has custom Dry Contact Alert 2 selected |
Yes |
T10+ |
|
||
|
6400 - 6470 |
These are duplicate settings to 6190-6260 but for Dry Contact Alert 3 (if selected) |
6005 has custom Dry Contact Alert 3 selected |
Yes |
T10+ |
|
||
|
6500-6570 |
These are duplicate settings to 6190-6260 but for Dry Contact Alert 4 (if selected) |
6005 has custom Dry Contact Alert 4 selected |
Yes |
T10+ |
|
||
|
6600 |
Dry contacts |
Cool Lockout Delay Time |
|
6230, 6340, 6440, or 6540 set to lock out cool |
Yes |
T10+ |
See Dry Contact Alerts (ISU 6000- 6220) for operation details
|
|
6610 |
Dry contacts |
Cool lockout maximum indoor temperature |
|
Yes |
T10+ |
||
|
6620 |
Dry contacts |
Heat Lockout Delay Time |
|
6230, 6340, 6440, or 6540 set to lock out Heat |
Yes |
T10+ |
|
|
6630 |
Dry contacts |
Heat lockout minimum indoor temperature |
|
Yes |
T10+ |
||
|
6640 |
Dry contacts |
Minimum Off Time |
|
6230, 6340, 6440, or 6540 set to lock out Heat or Cool |
Yes |
T10+ |
|
|
7000 |
Filtration |
Filter type |
|
|
No |
Both |
|
|
7020 |
Filtration |
Number of air filters |
|
7000 = media |
No |
Both |
|
|
7110 |
Filtration |
Replacement reminders |
Air Filter 1 settings and Air Filter 2 settings:
|
7020 = 1 or 2 |
No |
Both |
|
|
7020 = 2 |
No |
Both |
|
||||
|
7120 |
Filtration |
Electronic Air Cleaner Reminders |
Clean cells, options:
|
7000 = electric |
No |
Both |
|
|
Clean Pre-filters, options:
|
No |
Both |
|
||||
|
Replace Post-filters, options:
|
No |
Both |
|
||||
|
8000 |
Humidification |
What type of humidifier do you have? |
|
U contacts not already used |
No |
Both |
|
|
8010 |
Humidification |
What sensors will be used for Humidification control |
|
8000 = other than None & Wireless sensor connected to thermostat |
No |
T10+ |
|
|
8030 |
Humidification |
What terminals are wired to the humidifier? |
|
|
Yes |
T10+ |
Thermostat U1 only shown when EIM not used |
|
8050 |
Humidification |
Humidification Window Protection |
|
1060 & 8000 = other than "none". Need wired or wireless outdoor sensor for this feature |
No |
Both |
SeeWindow Protection for more details |
|
8060 |
Humidification |
System modes allowing humidification |
|
8000 = other than "None". (Cool option only when discharge sensor selected ISU 5000) |
No |
Both (cool only for T10+ with DATS) |
Multiple selections allowed |
|
8070 |
Humidification |
Humidification control |
|
8000 set to other than None |
No |
Both |
|
|
8080 |
Humidification |
Humidifier Lockout |
|
8060 set to Cool |
No |
T10+ |
|
|
8095 |
Humidification |
Humidifier Lockouts Dry Contacts |
|
8000 = steam, by-pass or fan powered, & 6000 = full drain pan or water leak, OR 6005 is set for custom Dry Contact Alert |
Yes |
T10+ |
This will lock out the humidifier when the associated Dry Contact Alert is active |
|
8100 |
Humidification |
Humidifier Pad replacement reminder |
|
8000 = none, or bypass or fan powered |
No |
Both |
|
|
8100 |
Humidification |
Clean tank/Water Filter replacement Reminder |
|
8000 = steam |
No |
Both |
|
|
9000 |
Dehumidification |
What type of dehumidification equipment do you have? |
Residential:
Commercial:
|
A/C with low speed fan, Whole House Dehumidifier/Dehumidifier, & Hot Gas Bypass only shown if U contacts are available |
No |
Commercial only for T10+ |
|
|
9005 |
Dehumidification |
Dehumidification Fan speed priority |
|
9000 = A/C with Low Speed Fan |
No |
T10+ |
|
|
9010 |
Dehumidification
|
What sensors will be used for Humidification control |
|
9000 = A/C with Low Speed Fan, Whole House Dehumidifier, or Hot Gas Bypass |
No |
T10+ |
|
|
9040 |
Dehumidification
|
What terminals are wired to the dehumidification equipment? |
|
9000 = A/C with Low Speed Fan or Whole House Dehumidifier |
Yes |
T10+ |
Thermostat U1 only shown when EIM not used |
|
9050 |
Dehumidification
|
Dehumidification Equipment Setup |
|
9000 = Low Speed Fan or Hot Gas Bypass |
No |
Both |
|
|
9070 |
Dehumidification
|
Dehumidification - Overcooling Limit |
|
9000 = A/C with High or Low Speed Fan |
No |
Both |
If Celsius is selected in ISU 1050, the Celsius temperatures seen in the Options column at left are presented. |
|
9080 |
Dehumidification
|
Control Method |
|
OffISU 1010 = commercial & 9000 = AC with high speed fan, AC with low speed fan, or Hot gas bypass. |
No |
T10+ |
Some of these settings originated with the Factory/
ISU 9080-9100 were part of this update.
The T10+ will receive this OTA update when the thermostat is connected to WiFi and registered to an account. Note that the OTA update may take as long as one day after connection and registration.
|
|
9090 |
Dehumidification
|
Dehumidification Minimum On Time |
|
9080 = other than Basic |
No |
T10+ |
|
|
9100 |
Dehumidification
|
High Humidity Comfort Reset Setting |
0 - 5°in 1°F increments (0.0 - 2.5°Cin 0.5°C increments) |
9080 = one of the Comfort Reset settings |
No |
T10+ |
|
|
9120 |
Dehumidification
|
System modes allowing dehumidification |
|
9000 - Whole House Dehumidifier |
No |
Both |
|
|
9130 |
Dehumidification
|
Dehumidifier Fan Control |
|
9000 - Whole House Dehumidifier |
No |
Both |
|
|
9140 |
Dehumidification
|
Dehumidifier Lockout |
|
9000 - Whole House Dehumidifier |
No |
Both |
|
|
9145 |
Dehumidification
|
Dehumidifier lockout dry contact |
Custom Alert 1 - Custom Alert 4 (options depend on 6005 settings) |
ISU 6005 is set for a custom dry contact alert |
Yes |
T10+ |
If enabled, the dehumidifier will lock out whenever the selected Dry Contact Alert is active |
|
9180 |
Dehumidification
|
Dehumidification - Away mode |
|
|
No |
T10+ |
|
|
9190 |
Dehumidification
|
Dehumidification Away mode Fan Control |
|
9180 = allowed |
No |
T10+ |
|
|
9200 |
Dehumidification
|
Dehumidification Away mode low limit temperature setting |
70°F-80°F (21.0°C-26.5°C) |
9180 = allowed |
No |
T10+ |
The dehumidification Away mode setting can restrict this |
|
Dehumidification Away Mode Temperature Setting |
70°F to 99°F (21.0°C to 37.0°C) |
9180 = allowed |
No |
T10+ |
The dehumidification Away mode Low Limit setting can restrict this |
||
|
Dehumidification Away Mode Dehumidification Setting |
40% - 70% |
9180 = allowed |
No |
T10+ |
|
||
|
9210 |
Dehumidification
|
Dehumidifier Filter replacement reminder |
|
|
No |
Both |
|
|
10000 |
Ventilation |
Ventilation Type |
|
ERV/HRV or Damper needs available U contacts. Passive Fan is not an option for Radiant Heat Only. |
No |
Both |
|
|
10005 |
Ventilation |
Ventilator Model number |
Other model
|
ISU 10000 set to ERV/ HRV |
No |
T10+ |
See Ventilation. |
|
10020 |
Ventilation |
What terminals are wired to the ventilation equipment? |
|
10000 = ERV/HRV or Fresh Air Damper |
Yes |
T10+ |
Thermostat U1 only shown when EIM not used. |
|
10050 |
Ventilation |
Ventilation control method |
|
10000 = ERV/HRV or Fresh Air Damper |
No |
Both |
|
|
10060 |
Ventilation |
Ventilation Fan control |
|
10000 = ERV/HRV or Fresh Air Damper and 8000 set for Humidifier |
No |
Both |
|
|
10065 |
Ventilation |
Turn on ventilation dry contacts |
|
ISU 6005 is set for a custom dry contact alert & ISU 10140 isn’t selected for the same custom alert. |
Yes |
T10+ |
If enabled, the ventilator will come on whenever the selected Dry Contact Alert is active |
|
10090 |
Ventilation |
Ventilation House Size |
Number of Bedrooms 1-6 |
10050 = ASHRAE |
No |
Both |
|
|
Size of house:
|
10050 = ASHRAE |
No |
Both |
|
|||
|
10100 |
Ventilation |
Enter Equipment Ventilation Rate |
|
10050 = ASHRAE |
No |
Both |
Fixed setting and not adjustable if VNT5070 or VNT5200 is selected for 10005. This setting also indicates whether or not you meet ASHRAE standards if ISU 10050 = ASHRAE based on ISU 10090 settings |
|
10120 |
Ventilation |
Ventilation Percent On Time |
10% - 100% (30% default) |
10050 + % on time |
No |
Both |
|
|
10125 |
Ventilation |
Ventilation Priority |
|
10050 = ASHRAE |
No |
Both |
|
|
10130 |
Ventilation |
Outdoor condition lockouts |
Low Temperature = off, -20F to 40F (off, -29.0 - 4.5C) |
10000 = ERV/HRV or Fesh air damper & 1060 (outdoor temperature) = other than "None" |
No |
Both |
|
|
High Temperature = off, 80F to 110F (off, 26.5C-43,5C) |
No |
Both |
|
||||
|
High Dew point = off, 65F - 85F (Off, 18.5C-29.5C) |
1060 = Internet or Wireless |
No |
Both |
|
|||
|
10140 |
Ventilation |
Lockout Ventilation on Humidification or dehumidification calls |
|
10000 set to other than "none and 8000 set for humidifier and/or 9000 set for dehumidifier |
Yes |
T10+ |
|
|
10145 |
Ventilation |
Ventilation lockout dry contacts |
|
ISU 6005 is set for a custom dry contact alert & ISU 10065 isn’t selected for the same custom alert. |
Yes |
T10+ |
If enabled, the ventilator will be locked out whenever the selected Dry Contact Alert is active |
|
10150 |
Ventilation |
Lockout Ventilation during Sleep mode |
|
|
No |
Both |
|
|
10160 |
Ventilation |
Ventilate on high indoor humidity |
Off, On (Heat only) |
8000 set for humidifier and 10000 set for ventilator |
Yes |
T10+ |
|
|
10170 |
Ventilation |
Ventilation Reminders |
Clean core = Off, 3, 6, 9, 12, calendar months |
Core only shown if 100 = ERV/HRV. Filter reminder always shown. |
No |
Both |
|
|
Clean filter = Off, 3, 6, 9, 12, calendar months |
|
No |
Both |
|
|||
|
11000 |
UV Devices |
Number of UV Devices |
0, 1, 2 |
|
No |
Both |
|
|
11050 |
UV Devices |
UV Bulb Replacement Reminders |
Replace UV Bulb 1 = Off, 6, 12, 24 calendar months |
11000 = 1 or 2 |
No |
Both |
|
|
Replace UV Bulb 2 = Off, 6, 12, 24 calendar months |
11000 = 2 |
No |
Both |
|
|||
|
14005 |
Idle screen Style |
Idle screen Style |
|
|
No |
Both |
|
|
14010 |
Clock Format |
Clock Format |
|
|
No |
Both |
|
|
14015 |
Daylight Savings Time |
Daylight Savings Time |
|
|
No |
Both |
|
|
14020 |
Display Offsets |
Indoor Display Offsets |
Indoor Temperature: (-3 to 3) in 1 F increment(-1.5 to 1.5) in 0.5C increment |
|
No |
Both |
The display offset is applied to the Home screen, not the Priority screen. This offset is not associated with any individual sensor. |
|
Indoor Humidity: -12% to 12% RH |
|
No |
Both |
||||
|
14030 |
Display Offsets |
Outdoor Display Offsets |
Outdoor Temperature: (-3 to 3) in 1 F increment(-1.5 to 1.5) in 0.5C increment |
|
No |
T10+ |
T10+ Linked to C7089R3013 wireless outdoor sensor |
|
Outdoor Humidity: -12% to 12% RH |
|
||||||
|
14050 |
Indoor humidity |
Show indoor humidity on home screen |
Yes, No |
|
No |
T10+ |
If set to control a humidifier or dehumidifier, the T10+ will still show the indoor humidity reading under the Humidity and Dehumidity setting screens |
|
15000 |
Dealer Information |
Dealer Information |
Enter Company name, phone number, website, email, message |
|
No |
Both |
|